MULTI M-2010+ Digital Clamp Tester (CE)

Product Overview

The MULTI M-2010+ Digital Clamp Tester is a multifunctional AC current measuring instrument designed for electrical inspection, testing and maintenance applications. Featuring a 40 mm diameter current transformer (CT) jaw, it measures AC current across three selectable ranges: 20 A, 200 A and 1000 A.

In addition to AC current measurement, the M-2010+ provides AC voltage, DC voltage and resistance measurement through its test leads. It also includes diode testing and an audible continuity check, making it a practical instrument for a range of electrical testing tasks.

The tester features a 3½-digit LCD with a maximum reading of 1999, data hold and automatic power-off functions. Its compact design and supplied hard carrying case support convenient handling and transportation.

Key Features

  • AC current measurement up to 1000 A

  • 40 mm diameter clamp jaw

  • Three manual AC current ranges: 20 A, 200 A and 1000 A

  • AC voltage measurement

  • DC voltage measurement

  • Resistance measurement up to 20 MΩ

  • Diode testing function

  • Audible continuity check

  • 3½-digit LCD display, maximum reading 1999

  • Data hold function

  • Automatic power-off after approximately 10 minutes

  • Low battery indication

  • CE model

  • Conforms to the manufacturer's specified IEC safety requirements

Measurement Functions

AC Current Measurement (ACA)

The M-2010+ measures alternating current using its 40 mm clamp-type current transformer. Three manually selectable ranges are available:

  • 20 A

  • 200 A

  • 1000 A

The maximum specified AC current input is 1000 A. The conductor should be positioned at the centre of the clamp, and the clamp should enclose only one conductor during measurement.

AC Voltage Measurement (ACV)

AC voltage can be measured using the supplied test leads. The instrument provides automatic range selection with measurement ranges up to 1000 V AC.

DC Voltage Measurement (DCV)

The tester also supports DC voltage measurement through its test leads, with automatic range selection up to 1000 V DC.

Resistance Measurement (Ω)

The resistance function provides automatic range selection from 200 Ω up to 20 MΩ, supporting general electrical testing and troubleshooting.

Diode and Continuity Testing

Additional functions include diode testing and an audible continuity check. The continuity buzzer operates when the measured circuit resistance is below approximately 300 Ω.

Applications

The MULTI M-2010+ can be used for:

  • AC current measurement in electrical conductors

  • Electrical equipment inspection

  • Electrical maintenance and troubleshooting

  • AC and DC voltage checks

  • Resistance measurement

  • Diode testing

  • Continuity checks

  • General electrical testing within the manufacturer's specified operating and safety limits

Safety and Operating Instructions

The M-2010+ is specified by the manufacturer as meeting IEC 61010-1 and IEC 61010-2-032 safety requirements, with Installation Category IV, 600 V phase-to-earth.

Important safety warning: The manufacturer explicitly warns that the instrument must not be used to measure power lines carrying more than 250 V and states that it should not be used to measure power lines because transient voltage spikes may occur. The manual also prohibits measurements on uninsulated conductors or busbars.

Always observe the maximum input limits and read the instruction manual before operating the instrument. Resistance and diode measurements must only be performed on de-energized circuits.

 

Extra Information

Brand:
Multi
Brand:
MULTI
Product Type:
AC Digital Clamp Tester
AC Current Range:
20 A / 200 A / 1000 A
AC Current Accuracy:
±1.5% rdg ±10 dgt (20 A / 200 A); ±1.0% rdg ±8 dgt (1000 A)
AC Voltage Range:
2 V / 20 V / 200 V / 1000 V
DC Voltage Range:
2 V / 20 V / 200 V / 1000 V
Voltage Accuracy:
±0.7% rdg ±5 dgt (2 V); ±1.2% rdg ±5 dgt (20 V / 200 V / 1000 V)
Resistance Range:
200 Ω / 2 kΩ / 20 kΩ / 200 kΩ / 2000 kΩ / 20 MΩ
Resistance Accuracy:
±1.2% rdg ±5 dgt (up to 2000 kΩ); ±3.0% rdg ±10 dgt (20 MΩ)
Clamp Jaw Opening:
40 mm diameter
Display:
3½-digit LCD, maximum reading 1999
Continuity Test:
Audible buzzer, below approx. 300 Ω
Diode Test:
Available
Data Hold:
Yes
Auto Power Off:
Approx. 10 minutes
Sampling Rate:
2 times/sec
Measuring Method:
Dual slope integration
Safety Standards:
IEC 61010-1; IEC 61010-2-032
Installation Category:
CAT IV 600 V phase-to-earth
EMC Standard:
EN 61326
Withstanding Voltage:
AC 5500 V for 1 minute
Operating Temperature:
0°C to +40°C
Operating Humidity:
Maximum 80% RH, non-condensing
Storage Temperature:
−10°C to +60°C
Storage Humidity:
Maximum 70% RH, non-condensing
Power Supply:
2 × AAA 1.5 V batteries
Power Consumption:
Approx. 3.5 mW
Battery Life:
Approx. 500 hours continuous
Dimensions:
70 × 223 × 34 mm
Product Weight:
Approx. 425 g