Description
The DF Electric 14×51 gG Cylindrical Fuse Link – Without Indicator is designed for general-purpose protection against overloads and short circuits in low-voltage electrical installations. It is suitable for applications requiring protection of cables, power lines and electrical equipment, including industrial distribution panels, switchboards and electrical control assemblies where the selected fuse rating matches the circuit requirements.
Designed for Industrial Electrical Protection
The gG operating class is intended for general protection against both overloads and short circuits. Selecting the correct rated current and voltage is essential to ensure that the fuse is suitable for the circuit being protected. This 14×51 mm format provides a compact cylindrical fuse solution for compatible fuse holders and electrical assemblies.
Ceramic Body and Silver-Plated Copper Contacts
The fuse link features a ceramic body designed to withstand internal pressure and thermal shock. According to DF Electric, its specially designed melting elements help limit ageing and maintain the fuse's operating characteristics over time. The contacts are made of silver-plated copper.
High Breaking Capacity
The 14×51 gG range offers a rated breaking capacity of 80 kA at 690 V AC and 120 kA at 500 V AC and 400 V AC. These ratings support its use in electrical installations where the prospective short-circuit current and system voltage fall within the specified limits. The selected fuse must always be checked against the electrical design requirements.
Without Visual Fusing Indicator
This version does not include a visual indicator for identifying a fuse that has operated. It is the standard version of the 14×51 gG range and is offered separately from the versions with a visual indicator and with a striker. The correct version should be selected according to the inspection and signalling requirements of the installation.
Suitable for Compatible Fuse Holders
The 14×51 format is compatible with the DF Electric PMX 14×51 fuse holder range, subject to checking the holder's electrical ratings and installation requirements. The fuse is intended to be selected and installed by qualified personnel in accordance with the manufacturer's instructions and applicable electrical standards.
Selection and Installation Notes
Choose the rated current and voltage according to the circuit's operating conditions and required protection. The manufacturer specifies that when the ambient temperature exceeds 25°C, the maximum current must be derated. Installation must be carried out with the circuit de-energised and in accordance with applicable safety practices.
This product is supplied as the Without Indicator version. Rated-current availability depends on the selected variant.