Description
The DF Electric 14×51 aM Cylindrical Fuse Link with Striker is designed for short-circuit protection in motor circuits and other electrical applications with high inrush currents. Its aM operating class is intended for short-circuit protection and must be combined with a suitable overload protection device.
The integrated striker mechanism is designed to operate a compatible fuse holder equipped with a microswitch, allowing the fuse's operation to trigger a corresponding switching or signalling function when used with compatible equipment.
Applications
The aM fuse-link class is intended for short-circuit protection in motor circuits and other loads with high inrush currents. Its current-limiting characteristics support the protection of associated switching equipment when the fuse is correctly selected and coordinated with the circuit's overload protection.
The striker version is intended for use with compatible fuse holders incorporating a microswitch.
Construction
DF Electric's aM cylindrical fuse links feature a ceramic body designed to withstand internal pressure and thermal shock. The manufacturer specifies specially designed silver-plated melting elements to help maintain the fuse's operating characteristics over time.
Selection and Installation
Select the fuse link according to the required rated current, operating voltage, prospective short-circuit current, and the requirements of the protected equipment.
The selected fuse holder must be compatible with the 14×51 fuse-link size and the striker mechanism. Verify the holder's microswitch compatibility and the complete protection arrangement before installation.
As an aM fuse link provides short-circuit protection rather than complete overload protection, a suitable overload protection device must also be provided.